V-PAC System Application Guidelines and Specifications
- System consists of 1 grid of UVC lamps between the cooling coil and 1 PCO panel
- Use when coil and drain pan cleaning is most the important and air stream VOC removal is not the main concern
- The PCO system works best in the air flow recirculation to the space mode
- Installation will be in the air stream down stream of the cooling coil
- System consists of 1 grid of UVC lamps between the cooling coil and 1 PCO panel
- Use when coil and drain pan cleaning is most the important and air stream VOC removal is not the main concern
- The PCO system works best in the air flow recirculation to the space mode
- Installation will be in the air stream down stream of the cooling coil
- System consists of 1 grid of UVC lamps between 2 PCO panels + 1 High VOC Adsorbent Carbon Panel (HVAP)
- For areas with VOC spikes and air recirculation will be less than 50%
- Effective for VOC spikes from casino cigarette smoke and aviation fuels
- Modular configuration allows for easy integration into new and existing heating, ventilation, and air conditioning (HVAC) systems
- Scalable design to fit any plenum size
- Photo catalytic panels (PCO) and High VOC Adsorbent Panels (HVAP) are designed for installation in standard filter tracks
- Negligible pressure drop / Up to 95% non-condensing
- Complete system will fit in an airflow length that is as little as 9”
- Virus, bacteria, VOC and odor reduction
- The PCO filter panels are made of aluminum honeycomb construction impregnated with a proprietary coating of titanium dioxide catalyst
- The activated carbon filter is preferably a 1” thick BPS Lite™ filter which housed in the same filter holding frame as the PCO (photo catalytic panels)
- Ambient temperature operation / Rated for temperature 30F to 150 F (4C to 57C)
- Energy savings through the reduction of outside air / Chemical free / No residual ozone
- Low power consumption / Long catalyst life/ Minimal maintenance requirements
System Requirements:
- One V-PAC System per air handling unit (minimum 10 ton recommended)
- V-PAC Systems available to 1, 2 or 3 Stages. (See V-PAC Application Guidelines above)
- One 20 amp circuit per V-PAC system
- 9” of airflow length to accommodate the V-PAC system
- Recommended 4-6 air exchanges per hour
12 x 12 x 1 / 12 x 24 x 1 / 24 x 24 x 1
Custom sizes also available
V-PAC System is available in a variety of configurations depending on concentration levels, percentages of outside air, and desired results. Our design team will assist in tailoring your system for the specific end-use application. Standard modular sizes available for configuring into any size duct cavity or AHU.
UVC Grid Sizes:
21” V MAX GRID Lamp Module: 120 VAC .45 A 240 VAC .20 A
33” V MAX GRID Lamp Module: 120 VAC .75 A 240 VAC .40 A
61” V MAX GRID Lamp Module: 120 VAC 1.30 A 240 VAC .60 A
Regulatory approvals:
ETL listed to UL/Canadian standards:
UL 1598/CSA 22.2 250 UL
1995/CSA 22.2 236 UL
153/CSA 22.2 12 for category ABQK
(Air Duct Mounted Accessories)